Insulating Boots
Related Tags :
Insulating BootsNo Search Result
Related Tags :
Insulating BootsMedium Voltage Insulating Boots. Cold applied unscreened elastomeric insulating boots (in Silicon or EPDM) are moulded parts, fitted over the connection between a cable lug and inline or right-angled equipment bushing, to improve phase-to-phase and phase-to-ground insulation. They are used in switchgear and transformer cable boxes where the air clearances are insufficient for normal operation or protect against flashover due to rodents or high humidity. The non-tracking elastomeric housing has excellent erosion resistance, dielectric properties, and environmental resistance, giving superb performance in areas of high humidity and electrical stresses.
Please connect with us
Parameter | Value |
---|---|
Suitable for indoor applications upto 17.5 kV system | |
Improves air clearances in confined boxes | |
Mounted on single or three core applications | |
Kit No: | Kit Contents |
CAB-RRL-KIT (for three core cable) | Elastomeric insulating boots, Silicon grease, Installation instruction |
E-CAB-KIT (for three core cable) |
Elastomeric insulating boots, Silicon grease, Installation instruction |
Parameter | Value |
---|---|
Maximum system voltage | 17.5 kV |
Basic impulse level | 75 / 95 kV |
AC high Voltage | 36kV for 1 minute |
Bushing diameter | 46 - 70 mm |
Bushing types | DIN, CEN ELEC, ANSI 400/630A |
Cable cross section | 35 – 400 mm² |
All products provided below with slider to find faster.