Specifications
Catalogue Code |
Connection Type |
MAIN |
TAP |
Dimensions Inch (mm) |
||||||
---|---|---|---|---|---|---|---|---|---|---|
Run |
Tap |
Dia. Inch (mm) |
AAC/CU |
ACSR |
Dia. Inch (mm) |
AAC/CU |
ACSR |
A |
C |
|
RHLA 2020 |
Al |
Al/Cu |
0.128-0.414 (3.25-10.51) |
#8 - 2/0 Str. |
#8 - 1/0 |
0.128-0.414 (3.25-10.51) |
#8 Sol. / 2/0 Str. |
#8 - 1/0 |
4.5 (114.3) |
2.85 (72.4) |
RHLA 4004 |
Al |
Al/Cu |
0.162-0.745 (4.11-18.92) |
#6 - 400 |
#6 - 397.5 (18/1) |
0.152-0.63 (3.86-16.0) |
#6 Sol - 4/0 Str. |
#6 - 3/0 |
6.7 (170.1) |
2.44 (61.0) |
Technical Information
Parameter |
---|
Installed on live line using insulated stick |
Suitable for different cable ranges, in copper, aluminium or ACSR |
Aluminium based conductors, it is recommended to use inhibitor paste antioxidation to prevent galvanic corrosion |
ROHS Complaint |
Material – High conductivity electrolytic aluminium |
Finish – Electro tin plated |
Recommended with copper conductors - solid, compact, compressed, concentric |
Related Products